Vis enkel innførsel

dc.contributor.advisorFolkestad, Tor Arne
dc.contributor.authorAmundsen, Asbjørn Hagset
dc.contributor.authorVada, Kristian Andre Thomassen
dc.date.accessioned2019-09-06T14:13:03Z
dc.date.available2019-09-06T14:13:03Z
dc.date.issued2019
dc.identifier.urihttp://hdl.handle.net/11250/2613777
dc.description.abstractDenne besvarelsen gikk ut på å benytte målte belastningsdata (AMS-data for et år), fremfor prognoserte, fra en fordelingstransformator til å kunne gjøre en mer presis beregning av tap og tapskostnader. Gruppen mottok for lite målerdata og det ble nødvendig å genere fiktive måleverdier for månedene som manglet basert på Statnett sine årsvariasjoner for effektforbruk. Man må derfor anta noe usikkerhet i resultatene. Det ble utarbeidet et beregningsverktøy i Microsoft Excel. Verktøyet gir informasjon om effekttap, brukstid for last, brukstid for tap og lastutnyttelse for transformatoren. Det ble utført en sammenligning mellom antatt og beregnet brukstid for tap. Antatt brukstid for tap ble satt til 4000 timer, mot beregnet brukstid for tap på 3000 timer. Vi ser fra resultatet i oppgaven at det kan være store forskjeller på antatt og beregnet brukstid for tap. De spesifikke tapskostnadene utgjorde henholdsvis 37997 kr mot 32571 kr over en analyseperiode på 30 år. Forskjellene i kostnader ble dermed relativt små i denne oppgaven, som kan sees i sammenheng med at størrelsen på transformatoren var 100kVA. Gevinsten av å beregne detaljerte tapskostnader for små transformatorer kan dermed diskuteres. Resultatet er et beregningsverktøy som kan gjøre en mer presis beregning av tap og tapskostnader for fordelingstransformatorer ved å benytte AMS-data.
dc.description.abstractThis thesis has investigated how to use measured load data (AMS-data for a year), instead of estimated, from a distribution transformer to be able to calculate more accurate power losses and loss costs for the transformer. The group did not receive the amount of data necessary and had to generate fictitious measurements for the missing months. The missing data was generated by using Statnett's annual variations in power consumption. Because of this we must assume some uncertainty in the results. A calculation tool was prepared in Microsoft Excel. The tool provides information about power losses, time of loss, time of load, and load utilization for the transformer. A comparison was made between assumed and calculated time of loss. The assumed time of loss was 4000 hours, compared to the calculated time of loss of 3000 hours. The result shows that there can be large differences in the assumed and calculated time of loss. The specific loss costs amounted to NOK 37997, and NOK 32571 over a period of 30 years. The differences in costs were thus relatively small, which can be seen in the context of the size of the transformer being 100kVA. The benefit of calculating detailed loss costs for small transformers can thus be discussed. The result is a calculation tool that can make a more accurate calculation of power losses and loss costs for distribution transformers using AMS-data.
dc.languagenob
dc.publisherNTNU
dc.titleFordelingstransformatorer og tapskostnader - Beregning av en mer detaljert modell for tapskostnader ved bruk av AMS-data
dc.typeBachelor thesis


Tilhørende fil(er)

Thumbnail
Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel