dc.contributor.authorSkjong, Espen
dc.contributor.authorSuul, Jon Are Wold
dc.contributor.authorMolinas Cabrera, Maria Marta
dc.contributor.authorJohansen, Tor Arne
dc.date.accessioned2016-05-12T13:15:39Z
dc.date.accessioned2016-05-20T12:25:31Z
dc.date.available2016-05-12T13:15:39Z
dc.date.available2016-05-20T12:25:31Z
dc.date.issued2016-05
dc.identifier.citationThe Renewable Energies and Power Quality Journal (RE&PQJ) 2016nb_NO
dc.identifier.issn2172-038X
dc.identifier.urihttp://hdl.handle.net/11250/2389946
dc.description.abstractThis paper discusses how an Active Power Filter (APF) can be utilized for system-wide harmonic mitigation in a microgrid with multiple sources of harmonic distortion located at different buses. A two-bus microgrid system with independent nonlinear loads at both buses is first investigated analytically, and it is demonstrated that it is possible to derive a harmonic current injection from the APF that will minimize the harmonic distortion at both buses. However, analytical optimization of the APF current will be sensitive to parameter variations, will deteriorate when the APF reaches current saturation and cannot be easily extended to larger systems with many loads at different buses. A more practically applicable method for calculating the APF current references, by using the framework of Model Predictive Control (MPC) is instead proposed for the investigated system. Under realistic operating conditions, this approach can obtain further improvement in the system-level harmonic mitigation. The characteristics and performances that are obtained with the analytical solution and the MPC-based control are assessed by time domain simulations in the Matlab/Simulink environment. The results clearly indicate how an MPC-based system-oriented compensation can maximize the utilization of a single APF in a multi-bus Microgrid.nb_NO
dc.language.isoengnb_NO
dc.publisherEuropean Association for the Development of Renewable Energies, Environment and Power Qualitynb_NO
dc.titleOptimal Compensation of Harmonic Propagation in a Multi-Bus Microgridnb_NO
dc.typeJournal articlenb_NO
dc.typePeer reviewednb_NO
dc.date.updated2016-05-12T13:15:39Z
dc.source.journalThe Renewable Energies and Power Quality Journal (RE&PQJ)nb_NO
dc.source.issue14nb_NO
dc.identifier.cristin1355343
dc.description.localcode© EA4EPQ. This is the authors’ accepted and refereed manuscript to the article.nb_NO