dc.description.abstractA full-size converter-fed synchronous machine (CFSM) technology is emerging as the most flexible system for pumped storage plants for efficient operation in a wide range of water flows, which is not the case in existing power plants with fixed-speed synchronous machines. This article presents steady-state control strategies to execute the variable speed operation of the pumped storage power plants in both turbine and pump mode using a full-size back-to-back converter. Furthermore, the starting method of the power plant in pump and turbine mode from a standstill is proposed. In addition, the seamless transition of operating modes from the turbine to pump mode and vice versa is presented, which is an essential feature required to adapt to the varying power generation from renewable energy sources like solar and wind. The behavior of the power plant during a voltage dip on ac grid, and the low-voltage ride-through (LVRT) capability in both turbine and pump modes are also presented. The proposed control strategies are experimentally verified with a 100 kVA machine and converter setup with an emulated reversible pump turbine (RPT) and waterways.en_US
dc.description.abstractControl Methods for Operation of Pumped Storage Plants With Full-Size Back-to-Back Converter Fed Synchronous Machinesen_US
dc.language.isoengen_US
dc.publisherIEEEen_US
dc.rightsNavngivelse 4.0 Internasjonal*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/deed.no*
dc.titleControl Methods for Operation of Pumped Storage Plants With Full-Size Back-to-Back Converter Fed Synchronous Machinesen_US
dc.title.alternativeControl Methods for Operation of Pumped Storage Plants With Full-Size Back-to-Back Converter Fed Synchronous Machinesen_US
dc.typePeer revieweden_US
dc.typeJournal articleen_US
dc.description.versionacceptedVersionen_US
dc.source.pagenumber6792-6803en_US
dc.source.volume59en_US
dc.source.journalIEEE transactions on industry applicationsen_US
dc.source.issue6en_US
dc.identifier.doi10.1109/TIA.2023.3305324
dc.identifier.cristin2167689
dc.relation.projectNorges forskningsråd: 257588en_US
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode1


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel

Navngivelse 4.0 Internasjonal
Med mindre annet er angitt, så er denne innførselen lisensiert som Navngivelse 4.0 Internasjonal