dc.description.abstractRandomly selected generator bars from a 50-year-old Norwegian hydro power generator were examined in this work. Typical non-destructive tests, as partial discharge and dissipation factor measurements were initially performed at both 50 Hz and 0.1 Hz. Then, the AC breakdown strength of the epoxy/mica/glass fibre reinforced bar insulation was measured by gradually increasing the voltage in steps of 5 kV with duration of 1 min until breakdown occurred. The field graded terminations were soaked in transformer oil during breakdown testing to prevent external surface flashovers. The AC breakdown voltage ranged between 60 kV and 75 kV, which corresponds to 8-10-fold the service voltage of 7.4 kV. No significant difference in breakdown voltage was observed between bars being located close to the high voltage or neutral terminal during service. This indicates minor degradation caused by the AC service stress, even after 50 years in service. No correlations were found between the measured breakdown voltage and the diagnostic partial discharge activity and dissipation factor measurements.en_US
dc.description.abstractAC Breakdown Voltage of 50-Year-Old Service Aged Hydro Power Generator Stator Barsen_US
dc.language.isoengen_US
dc.rightsNavngivelse 4.0 Internasjonal*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/deed.no*
dc.titleAC Breakdown Voltage of 50-Year-Old Service Aged Hydro Power Generator Stator Barsen_US
dc.title.alternativeAC Breakdown Voltage of 50-Year-Old Service Aged Hydro Power Generator Stator Barsen_US
dc.typeJournal articleen_US
dc.typePeer revieweden_US
dc.description.versionpublishedVersionen_US
dc.source.volume27en_US
dc.source.journalProceedings of the Nordic Insulation Symposiumen_US
dc.source.issue1en_US
dc.identifier.doi10.5324/nordis.v27i1.4714
dc.identifier.cristin2040533
dc.relation.projectNorges forskningsråd: 255099en_US
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode1


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel

Navngivelse 4.0 Internasjonal
Med mindre annet er angitt, så er denne innførselen lisensiert som Navngivelse 4.0 Internasjonal