Dynamic simulation of simultaneous HVDC contingencies relevant for vulnerability assessment of the nordic power system
Chapter
Accepted version

View/ Open
Date
2019Metadata
Show full item recordCollections
- Institutt for elkraftteknikk [2633]
- Publikasjoner fra CRIStin - NTNU [41402]
Original version
10.1109/PTC.2019.8810863Abstract
Large power-infeed of individual HVDC interconnectors may make the power system vulnerable to contingencies involving multiple HVDC interconnectors. This paper describes and demonstrates an approach to quantitative vulnerability analysis applied to HVDC contingencies. We consider four barriers' ability to mitigate severe frequency drops: inertial response, frequency containment reserves, demand-side response and under-frequency load shedding. Demand-side response, implemented as fast reduction in loads in response to decreasing frequency, is given particular attention. The consequences of an HVDC contingency in the presence or absence of these barriers is analysed to assess the power system vulnerability. Results illustrate how in low-inertia operating states, a) large-scale load shedding may be inevitable after simultaneous outage occurrence of multiple HVDC interconnectors and b) that barriers may significantly reduce the amount of load shed. Demand-side response could be an effective barrier if the response time is low and a sufficiently large amount of load is involved.