JavaScript is disabled for your browser. Some features of this site may not work without it.

Online Assessment of Contact Erosion in High Voltage Gas Circuit Breakers based on different Physical Quantities

Mohammadhosein, Milad; Niayesh, Kaveh; Shayegani Akmal, Amir Abbas; Mohseni, Hossein
Journal article, Peer reviewed
Accepted version
Thumbnail
Åpne
online assessment of contact erosion.pdf (1.284Mb)
Permanent lenke
http://hdl.handle.net/11250/2588044
Utgivelsesdato
2018
Metadata
Vis full innførsel
Samlinger
  • Institutt for elkraftteknikk [1596]
  • Publikasjoner fra CRIStin - NTNU [20946]
Originalversjon
10.1109/TPWRD.2018.2883208
Sammendrag
In this paper, an effort has been made to evaluate the online condition of arc contacts as a vital component of interruption chamber in high voltage puffer type SF6 circuit breakers. The relationship between eroded mass caused by short-circuit current interruption and different thermal stress indices such as transferred electrical charge, current squared, and arc energy is investigated, by performing many experiments with different current amplitudes and arcing times. It is demonstrated that none of the known indices can solely determine mass erosion caused by the current interruption. Therefore, the equations including two of defined parameters are proposed to evaluate mass erosion. The method using arc energy and transferred electrical charge owns the highest accuracy in evaluating mass loss. However, considering the complexity of arc voltage measurements, a second method using current and arcing time can be also utilized. In addition, the development of erosion during the lifetime of arc contacts is studied. It is shown that arc roots tend to form on new uneroded areas of the contacts during current interruption, resulting in different erosion rates between the first few and subsequent interruptions due to change of morphology of the contacts after the first few switching operations.
Utgiver
Institute of Electrical and Electronics Engineers (IEEE)
Tidsskrift
IEEE Transactions on Power Delivery

Kontakt oss | Gi tilbakemelding

Personvernerklæring
DSpace software copyright © 2002-2019  DuraSpace

Levert av  Unit
 

 

Bla i

Hele arkivetDelarkiv og samlingerUtgivelsesdatoForfattereTitlerEmneordDokumenttyperTidsskrifterDenne samlingenUtgivelsesdatoForfattereTitlerEmneordDokumenttyperTidsskrifter

Min side

Logg inn

Statistikk

Besøksstatistikk

Kontakt oss | Gi tilbakemelding

Personvernerklæring
DSpace software copyright © 2002-2019  DuraSpace

Levert av  Unit