dc.description.abstractThe maximum allowed per unit value of the synchronous reactance of a synchronous generator is normally decided by the grid codes in order to maintain the stability of the system. For the converter-fed synchronous hydrogenerator, the steady state stability can be maintained by the frequency converter. In this paper the constraint on the synchronous reactance is relaxed from 1.2 per unit to 2.0 per unit and then removed altogether. The cost of the active materials and the net present value of the cost of losses are calculated for each case and compared. Three different nominal frequencies are also used to find which one gives the lowest total cost. The total generator cost is reduced when the synchronous reactance is increased. The lowest cost of the 50 Hz designs are lower than the cost of the 25 and 75 Hz designs.nb_NO
dc.language.isoengnb_NO
dc.publisherInstitute of Electrical and Electronics Engineers (IEEE)nb_NO
dc.relation.ispartof2017 IEEE International Electric Machines and Drives Conference - IEMDC
dc.titleEffects of lifting reactance requirements on the optimal design of converter-fed synchronous hydrogeneratorsnb_NO
dc.typeChapternb_NO
dc.typePeer reviewednb_NO
dc.description.versionacceptedVersionnb_NO
dc.identifier.doi10.1109/IEMDC.2017.8002085
dc.identifier.cristin1487802
dc.description.localcode© 2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.nb_NO
cristin.unitcode194,63,20,0
cristin.unitnameInstitutt for elkraftteknikk
cristin.ispublishedtrue
cristin.fulltextpostprint
cristin.qualitycode1


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel