Control of formaldehyde silver catalyst reactor system

Vo, Phuong Ny Lillian Nguyen
Master thesis
Thumbnail
URI
https://hdl.handle.net/11250/3092545
Date
2023
Metadata
Show full item record
Collections
  • Institutt for kjemisk prosessteknologi [1877]
Description
Full text not available
Abstract
I denne oppgaven ble det undersøkt om den nåværende temperaturreguleringen avDyneas formaldehyd sølvkatalysatorprosess kan forbedres. Den nåværende temperaturreguleringen har rom for forbedring, ettersom den strever i visse perioder. Oppgaven tar utgangspunkt i en eksisterende

matematisk dynamisk modell av prosessen, skrevet i MATLAB. Tre kontrollstrukturer ble implementert og studert: den nåværende tilbakekoblingen med valve position controller, tillegg

foroverkobling med input transformasjon og Nonlinear Model Predictive Control (NMPC).

Tilbakekoblings- og tillegg foroverkoblingsstrukturene ble implementert ved å kode dem inn

i modellen og det ble brukt modellens eksisterende løser, ode15s. NMPC ble implementert med

CasADI i MATLAB, hvor optimaliseringsproblemet ble løst ved hjelp av orthogonal collocation

metoden. Til slutt ble alle reguleringsstrukturene simulert, plottet og sammenlignet.

Resultatene viste at den foreslåtte tillegg foroverkoblingsstrukturen regulerte reaktortemperaturen

bedre enn den nåværende tilbakekoblingsstrukturen. Forbedringen skyldes strammere

regulering, som også forebygger metning og tap av regulering. NMPC viste seg å regulere

reaktortemperaturen enda bedre enn både tilbake- og tillegg foroverkobling, på grunn av dens

prediktive handling. Reguleringen var mer effektiv og reagerte tidligere, noe som førte til redusert

avvik i reaktortemperaturen fra settpunktet.

Den enkleste måten å forbedre temperaturreguleringen var å bruke de nye tuningparameterne

fra SIMC-regelen. Disse nye reguleringsinnstillingene førte til strammere regulering med

færre inngrep av sikkerhetstiltak. Denne endringen gir kanskje ikke den beste forbedringen, men

den kan på egen hånd betydelig styrke temperaturreguleringen.
 
This thesis aimed to research if the current temperature control of Dynea’s formaldehyde silver

catalyst process could be improved. The current control has room for improvement as it

struggles at certain periods, especially during transient operation. The study started off with an

existing mathematical dynamic model of the process, written in MATLAB. Three control structures

were implemented and studied: the current feedback control with valve position controller,

added feedforward control with input transformation and Nonlinear Model Predictive Control

(NMPC).

The feedback and added feedforward control structures were implemented by coding them

on top of the model and used with the existing solver, ode15s. NMPC was implemented with

CasADI in MATLAB, where the optimization problem was solved using the orthogonal collocation

method. Finally, all control structures were simulated, plotted and compared.

The results showed that the proposed added feedforward structure was able to control the

reactor temperature better than the existing feedback control. This improvement was due to

tighter control, which also prevents saturation and loss of control. Furthermore, NMPC appeared

to control the reactor temperature even better than both the feedback and added feedforward

structures, due to its predictive action. The control was more effective and reacted earlier, resulting

in reduced deviation in the reactor temperature from the setpoint.

The simplest way to improve the temperature control was to use the new tuning parameters

from the SIMC-rule. These new control settings resulted in tighter control with fewer interventions

of safety measures. While this change may not yield the best improvement, it could

significantly boost the temperature control on its own.
 
Publisher
NTNU

Contact Us | Send Feedback

Privacy policy
DSpace software copyright © 2002-2019  DuraSpace

Service from  Unit
 

 

Browse

ArchiveCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsDocument TypesJournalsThis CollectionBy Issue DateAuthorsTitlesSubjectsDocument TypesJournals

My Account

Login

Statistics

View Usage Statistics

Contact Us | Send Feedback

Privacy policy
DSpace software copyright © 2002-2019  DuraSpace

Service from  Unit