Vis enkel innførsel

dc.contributor.authorGöthner, Fredrik T. B. W.
dc.contributor.authorMidtgård, Ole-Morten
dc.contributor.authorTorres Olguin, Raymundo E.
dc.contributor.authorD'Arco, Salvatore
dc.date.accessioned2019-03-20T09:15:51Z
dc.date.available2019-03-20T09:15:51Z
dc.date.created2018-10-29T10:56:58Z
dc.date.issued2018
dc.identifier.isbn978-1-5386-5186-5
dc.identifier.urihttp://hdl.handle.net/11250/2590763
dc.description.abstractDroop control has shown promising results for decentralized power sharing in microgrids. However, the basic scheme can suffer from unequal reactive power sharing power due to differing line impedances between converters and due to the predominantly resistive nature of low voltage networks. Virtual impedances are able to mitigate these drawbacks, and are mostly implemented using a quasi-stationary approach. This approach replicates an impedance in steady state, but transients of the load current are only partly reproduced. This paper discusses the effect of including the transient term of the virtual impedance. A state-space small-signal model is derived in order to show the effect of including the transient virtual impedance. Simulations of a two-inverter microgrid are also shown to test the model and offer a numerical example. Both modal analysis on the small-signal model and the results from the simulation indicate improved damping when including the transient virtual impedance.nb_NO
dc.language.isoengnb_NO
dc.publisherInstitute of Electrical and Electronics Engineers (IEEE)nb_NO
dc.relation.ispartof2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe - EEEIC/I&CPS Europe
dc.titleEffect of Including Transient Virtual Impedance in Droop-Controlled Microgridsnb_NO
dc.typeChapternb_NO
dc.description.versionacceptedVersionnb_NO
dc.identifier.doi10.1109/EEEIC.2018.8493932
dc.identifier.cristin1624347
dc.relation.projectNorges forskningsråd: 247626nb_NO
dc.description.localcode© 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.nb_NO
cristin.unitcode194,63,20,0
cristin.unitnameInstitutt for elkraftteknikk
cristin.ispublishedtrue
cristin.fulltextpreprint
cristin.qualitycode1