Advantage of CO2 heat pump chiller for the application in Indian hotels
Reddy, Y. Siva Kumar; Elarga, Hagar Hassan Hassanein Hassan; Gururchethan, A.M.; Maiya, M.P.; Hafner, Armin
Chapter
Accepted version
Permanent lenke
https://hdl.handle.net/11250/3120199Utgivelsesdato
2023Metadata
Vis full innførselSamlinger
Sammendrag
Hotels in India conventionally use diesel-fired hot water generators to meet hot water demands at 46°C. These are inefficient and also release high emissions. This study focuses on the energy saving and emission reduction potentials of a CO2 heat pump chiller system for such an application. An ejector-based system of 50 kW heating capacity is proposed for a typical hotel having a hot water demand of 40 m3 /day with a 5 m3 thermal storage tank (TST). The heat pump produces the hot water at 68°C which is stored in the proposed TST. As per the demand, the hot water from the TST will be supplied to two existing 5 m3 hot water supply tanks (one for rooms and the other for the kitchen) after being mixed with cold water to reach the required temperature (46°C). The system also supplements up to 3.2% of the cooling demand of the hotel by contributing chilled water at 7°C. The proposed system reduces the operating cost and CO2 emissions to approximately 10 and 30%, respectively of the existing set-up. Return on investment is found to be less than 2 years. Keywords: Ejector, R744, Transcritical, DHW, Thermal storage, Energy savings Advantage of CO2 heat pump chiller for the application in Indian hotels