Time-varying coherency study using TFC
Chapter
Accepted version
Permanent lenke
http://hdl.handle.net/11250/2482303Utgivelsesdato
2017Metadata
Vis full innførselSamlinger
- Institutt for elkraftteknikk [2414]
- Publikasjoner fra CRIStin - NTNU [37247]
Originalversjon
10.1109/PTC.2017.7980849Sammendrag
An assessment of the dynamic interactions between generators will provide valuable information which could improve control action and hence maintain stability in the interconnected system. The paper presents the study on dynamic interaction in terms of coherency established among the generators following a particular event. Time Frequency Coherency (TFC) method is applied to trace the coherency among the generators. The dominant inter-area modes on which TFC is applied has been extracted from empirical mode decomposition of the swing curve. The phase difference between the dominant modes will verify and refine the coherency results. The potential of TFC in power system application has been evaluated on test cases, power system model & Phasor Measurement Unit (PMU) signals.